Αριθμός ανταλλακτικού
Αποστρατιωτικοποίηση
Διάρκεια ζωής
UOM
NIIN
Αριθμός ανταλλακτικού:
lm2450
NSN
Εθνικός αριθμός αποθέματος:
TXT
Περιγραφή:
Circuit Breaker Tripper
Κωδικός ονόματος στοιχείου:
04558
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Rectangular dimensional envelope
MRC:
The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.ABHP
Overall Length:
7.500 inches
MRC:
The distance measured in a straight line from the bottom to the top of an item.ABKW
Overall Height:
4.250 inches
MRC:
An overall measurement taken at right angles to the length of an item,in distinction from thickness.ABMK
Overall Width:
5.250 inches
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
2
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
6 terminal
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
450.0 amperes ac all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
600.0 ac all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Magnetic all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Instantaneous all locations and time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
The basic internal electrical configuration of the trip mechanism.CPSM
Internal Trip Release Configuration:
Series trip all locations
MRC:
The length of time,expressed in seconds,that an overload may exist before the device will trip at a specified continuous current.CQWN
Trip Delay Time In Seconds Per Rated Continuous Current:
125.000 at 200 pct all locations and 720.000 at 200 pct all locations
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 all locations
MRC:
Indicates the type and number of terminals for providing electrical connection.TTQY
Terminal Type And Quantity:
6 compression