Αριθμός ανταλλακτικού
Αποστρατιωτικοποίηση
Διάρκεια ζωής
UOM
NIIN
Αριθμός ανταλλακτικού:
m39019-3-121
NSN
Εθνικός αριθμός αποθέματος:
TXT
Περιγραφή:
Circuit Breaker
Κωδικός ονόματος στοιχείου:
00136
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Multipole-single actuator type
MRC:
A measurement of the longest dimension of a bushing,in distinction from width.ABXD
Bushing Length:
Between 0.332 inches and 0.380 inches
MRC:
A measurement of the longest dimension of the body,in distinction from width.ADAQ
Body Length:
1.562 inches
MRC:
A measurement taken at right angles to the length of the body,in distinction from thickness.ADAT
Body Width:
1.281 inches
MRC:
The center to center distance between terminals parallel to the length of the item.AEBP
Center To Center Distance Between Terminals Parallel To Length:
0.906 inches
MRC:
The center to center distance between terminals parallel to the width of the item.AEBQ
Center To Center Distance Between Terminals Parallel To Width:
0.625 inches
Mounting Surface To Terminal End Distance:
1.828 inches
MRC:
The number of poles included in the item.AKPX
Pole Quantity:
2
MRC:
Indicates the type and number of facilities by which the item is mounted.AXHR
Mounting Facility Type And Quantity:
1 threaded bushing w/panel seal
MRC:
Those features,not otherwise specified,which may be required for proper functioning of the item.CBBL
Features Provided:
High inrush protection
MRC:
The maximum current load that each pole is rated to carry continuously.CPLM
Maximum Continuous Load Current Rating Per Pole:
12.5 amperes ac all locations and 12.5 amperes dc all locations
MRC:
Indicates the type and value of operating voltage for which each pole is designed to operate,expressed in volts.CPRF
Operating Voltage Type And Rating Per Pole In Volts:
240.0 ac all locations and 50.0 dc all locations
MRC:
Indicates the type and value of the maximum short circuit current that the item will successfully interrupt,per pole,at the specified rated voltage,expressed in amperes.CPRG
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps:
100.0 ac all locations and 175.0 ac all locations and 100.0 dc all locations
MRC:
Indicates the type of electrical condition that will cause the device to trip.CPRH
Circuit Protection Type:
Overcurrent all locations
MRC:
The means by which the trip mechanism is released.CPRJ
Trip Release Method:
Magnetic all locations
MRC:
Denotes the type of trip release action.CPRL
Trip Release Characteristic:
Time delay all locations
MRC:
The continuous current rating per pole at which the device must trip in a specified time,expressed in percent.CPRN
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent:
125.0 all locations
MRC:
The means provided to reposition the mechanism so that the device is ready to function.CPRQ
Reset Method:
Manual
MRC:
Indicates the type of mechanism provided for tripping main contacts.CPRR
Main Contact Tripping Mechanism Type:
Trip free
MRC:
The basic internal electrical configuration of the trip mechanism.CPSM
Internal Trip Release Configuration:
Series trip all locations
MRC:
A designation that is used for the purpose of general identification of the thread.CQJX
Thread Size:
0.375 inches
MRC:
Indicates the type of protection for which the inclosure is designed.CQXF
Inclosure Protection Type For Which Designed:
Hermetically sealed
MRC:
The cycles per second /hertz/ of the alternating current.FREQ
Frequency In Hertz:
60.0 all locations or 400.0 all locations
MRC:
A designation distinguishing one group of thread diameter-pitch combinations from another by the number of threads per measurement scale for a specific diameter.THSD
Thread Series Designator:
Unc