Αριθμός ανταλλακτικού
Αποστρατιωτικοποίηση
Διάρκεια ζωής
UOM
NIIN
Αριθμός ανταλλακτικού:
wf791
NSN
Εθνικός αριθμός αποθέματος:
TXT
Περιγραφή:
Cartridge Fuse
Κωδικός ονόματος στοιχείου:
00248
MRC:
The style designation indicating the configuration that most nearly corresponds to the appearance of the body.AAQL
Body Style:
Knife blade type
MRC:
The dimension measured along the longitudinal axis with terminated points at the extreme ends of the item.ABHP
Overall Length:
11.625 inches
MRC:
A measurement of the longest dimension of a terminal,in distinction from width.ABJT
Terminal Length:
1.875 inches
MRC:
A measurement of the longest straight line across a circular cross-sectional plane.ADAV
Overall Diameter:
2.500 inches
MRC:
The element,compound,or mixture of which the case is fabricated,excluding any surface treatment.ADTV
Case Material:
Fiber
MRC:
The maximum direct current,or root mean square current at rated frequency,that an item will carry continuously.AEBJ
Continuous Current Rating In Amps:
400.000
MRC:
A measurement taken at right angles to the length of the terminal,in distinction from thickness.AFWW
Terminal Width:
1.625 inches
MRC:
A measurement of the smallest dimension of the terminal,in distinction from length or width.AFWY
Terminal Thickness:
0.250 inches
MRC:
The maximum voltage rating at which the item is designed to operate in an alternating current and/or direct current circuit,expressed in volts.AFXE
Maximum Voltage Rating In Volts:
600.0 dc
MRC:
Indicates the type of over-current conditions that an item is designed to withstand indicated by the speed of circuit interruption.AFXF
Circuit Over-current Interruption Type:
Time delay
MRC:
The means in which the item signals the interruption of a circuit.AFXH
Interruption Indicator Method:
Opaque body
MRC:
Those features,not otherwise specified,which may be required for proper functioning of the item.CBBL
Features Provided:
Renewable fusible element
MRC:
The time elapsing before circuit interruption of an item operated at a specified percent of its normal current rating,expressed in seconds.CQPB
Circuit Over-current Interruption Delay Time In Seconds:
82.0 250 pct of current rating and 6.0 500 pct of current rating
MRC:
The maximum rated current at which the item will interrupt or short circuit,expressed in amperes.CSQN
Short-circuit/interrupt Current Rating In Amps:
10000.0
MRC:
The number,letter,or symbol that indicates the type,style,grade,class,and the like,of an item in a nonidentifying specification or standard.ZZZT
Specification Or Standard:
1 type and b style and 2 class